| DC current range | 600.0 A / 2000 A; basic accuracy ±1.3% rdg. ±0.3 A (600 A range) |
|---|
| AC current range | 600.0 A / 2000 A (10 Hz to 1 kHz, True RMS); basic accuracy 45-66 Hz ±1.3% rdg. ±0.3 A (600 A range) |
|---|
| DC+AC current range | 600.0 A / 2000 A (10 Hz to 1 kHz, True RMS) |
|---|
| DC voltage range | 600.0 mV to 1000 V; with optional probe P2010, 600.0 V to 2000 V |
|---|
| AC voltage range | 6.000 V to 1000 V, 4 ranges (15 Hz to 1 kHz, True RMS) |
|---|
| Resistance range | 600.0 Ω to 6.000 MΩ, 5 ranges |
|---|
| Capacitance range | 1.000 μF to 1000 μF, 4 ranges |
|---|
| Frequency range | 9.999 Hz to 999.9 Hz, 3 ranges |
|---|
| Temperature (K) | -40.0 to 400.0 °C with optional K-type probe |
|---|
| Inrush current | Simultaneously measures RMS and crest values at motor startup; the meter detects the inrush duration itself |
|---|
| Crest factor | 600.0 A range: 3 or less; 2000 A range: 2.84 or less |
|---|
| Other functions | DC power, continuity check, diode check, automatic AC/DC detection, Max/Min/Average/PEAK MAX/PEAK MIN display, low-pass filter, display hold, auto hold, backlight, auto power save, buzzer, zero adjustment |
|---|
| Harmonic analysis | Voltage/current harmonic levels up to 30th order with the optional Z3210 wireless adapter and the free GENNECT Cross app |
|---|
| Wireless | Bluetooth via optional Wireless Adapter Z3210; transfers readings to a smartphone or tablet, or directly into an Excel template |
|---|
| Dustproof and waterproof | IP54 while in storage; IP20 during voltage measurement in completely dry conditions with the jaw closed |
|---|
| Power supply | 2x LR03 alkaline batteries; 40 hours continuous use (24 hours with Z3210 wireless in use) |
|---|
| Core jaw diameter | φ55 mm (2.17 in); jaw 92 mm W × 18 mm D |
|---|
| Dimensions and mass | 65 mm W × 250 mm H × 35 mm D, 530 g (18.7 oz) |
|---|
| Included accessories | Test Lead L9300, Carrying Case C0203, 2x LR03 alkaline batteries, instruction manual ×2, operating precautions |
|---|